Fluorescent Optical Fiber Temperature Measurement Solution for Power Contact in Power Grid Industry

Fluorescent Optical Fiber Temperature Measurement Solution for Power Contact in Power Grid Industry

1. Systematic Introduction

Transformers, switchgears, large motors and other high-voltage electrical equipment are the key equipment of power generation and transmission and transformation systems. Their safety, reliability and service life are crucial to the safe and reliable operation and life of the entire transmission and transformation system. Most of these high-voltage equipment are enclosed structure. They work in the environment of high voltage, high current and strong magnetic field for a long time. Some joints are heated due to aging or excessive contact resistance, which results in heat accumulation. Heating temperature rise increases the loss of power transmission system. If the heat dissipation is not good, it will endanger the normal operation of equipment, even cause faults. The adverse social impact and economic losses are immeasurable.

Taking transformer as an example, the accident rate of distribution transformer in operation is about 13%, in which the insulation aging is caused by the over temperature operation of windings, and the burnout and breakdown accidents of transformer windings account for a considerable proportion. In addition, many physical and chemical changes (such as partial discharge and partial overheating) in power transformer will cause the temperature parameters of transformer to change, which makes the temperature rise track of transformer different from that of normal operation. Based on the relationship between the aging rate and temperature of transformer according to the "6°rule" , the life of transformer can be reduced by half when the aging rate increases by one time at 6℃, and the life of transformer can be prolonged by one time when the temperature decreases by 6℃. For transformers, winding temperature plays a decisive role in the aging of insulation materials, so it is particularly important to accurately measure the winding temperature of transformers. With the continuous improvement of the automation level of safe power consumption and distribution network, besides monitoring the electrical parameters, direct monitoring of hot-spot temperature of high-voltage electrical equipment such as transformer/switchgear/transformer/large motor can improve the safe operation of equipment, prolong the insulation life of equipment, instantly judge the actual load capacity of equipment, and maximize the potential of transformer transmission and transformation to improve the installation. The economic benefits of preparation are of great significance.

The applications of fluorescent optical fiber temperature sensor in smart grid are as follows:

1. Power transformer winding temperature monitoring;

2. High-voltage switchgear: It can measure the temperature of plum blossom contacts and static contacts in switchgear, and even bury them in the conductive connection of insulating cylinder;

3. Temperature measurement of arc extinguishing chamber of high voltage circuit breaker;

4. Temperature monitoring of stator, bush and end confluence ring of large motor;

5. Direct monitoring of hot spot temperature of high voltage equipment such as large motor/transformer windings;

6. Other electrical equipment temperature online real-time monitoring.

image.png

 

As one of the future development directions of optical fiber temperature sensor, fluorescent optical fiber temperature sensor for smart grid also has the following advantages:

1. Immunization to electromagnetism, radio frequency and microwave;

2. No metal parts, no magnetization;

3. The measurement accuracy is high and the stability is good;

4. Good reliability and repeatability;

5. Structural tightness, long service life;

6. No calibration is required.

Compared with traditional temperature sensors, optical fiber temperature sensors have incomparable advantages. With the maturity of optical fiber temperature sensor technology and the establishment of technical regulations and related standards, fluorescent optical fiber temperature sensors will gradually replace traditional temperature sensors and become one of the most important means of temperature monitoring in power grid.

Fluorescent optical fiber temperature sensor is one of the key equipment in future smart grids. Developing smart grid industry based on various smart sensors is the extension and expansion of developing green new energy industry in China. It is a realistic need to combine China's industrial base, accelerate the transformation and upgrading of power equipment manufacturing industry, adapt to future competition, and achieve sustainable development. It is an inevitable choice for the high-end market and technological commanding point of power grid industry to strive for greater development space. It is an effective way and carrier to accelerate the integration of industrialization and information technology. It has very important practical significance and long-term strategic significance for stimulating economic development, optimizing industrial structure and transforming development mode.

 

2. Technical Advantages

The comparison of several main temperature measurement methods in the field of electric power at present:

2.1 Infrared Thermal Imaging Temperature Measurement System

Advantages:

1. Non-contact temperature measurement, and easy to operate;

2. Low cost.

Disadvantages:

1. The measurement is inaccurate, only the surface temperature can be measured; the real temperature of the internal hot spot cannot be measured;

2. Handheld, and cannot achieve online monitoring;

3. Artificial inspection, increase labor costs, the minimum annual labor costs of more than 100,000 Yuan.

2.2 Wireless Temperature Measurement System

Advantages:

1. Easy installation;

2. Low cost.

Disadvantages:

1. Poor reliability, with battery measurement, short life;

2. The insulation performance of cabinet is affected, so it cannot pass the test;

3. The large volume of the sensor affects the heat dissipation function;

4. The surface temperature can only be measured, but the real temperature inside the hot spot cannot be measured.

2.3 Fiber Bragg Grating Temperature Measurement System

Advantages:

1. Quasi-distributed temperature measurement can be realized, which is suitable for long-distance and large-area areas;

2. With optical fiber technology, the insulation performance is good.

Disadvantages:

1. Difficult to install;

2. Cannot achieve a single cabinet matching, cannot achieve in-situ display.

2.4 Fluorescent Optical Fiber Temperature Measurement System

Advantages:

1. Its performance is safe and reliable, and it can achieve calibration-free, good consistency, interchangeability and stability;

2. Long service life, maintenance-free. Minimum use of optical fiber sensors for 25 years;

3. The probe is small in size and can be used to measure the hot spot in depth, so as to realize the real and effective monitoring of the hot spot;

4. Anti-electromagnetic interference, good insulation performance, integrated into intelligent switchgear and passed the type test;

5. It can be displayed locally and integrated into the control system conveniently.

6. Easy installation and flexible networking;

7. High cost performance ratio.

Disadvantages:

1. The measuring distance is relatively short, usually in the order of 100 meters.

For the node temperature measurement of electrical equipment in power plants and substations, Herch’s fluorescent optical fiber temperature measurement has obvious advantages: no electrical interference, small size, long life, independent networking, and high reliability.

 

3. System Characteristics

Guarantee the ideal isolation of primary and secondary power, good linearity and high accuracy;

Multichannel transmission: The information collected by the system can be uploaded and dispatched by FTU, GPRS or communication management unit in the box, and the transmission mode can be flexibly selected according to the field environment;

Do not reduce the safety level of electrical equipment: Temperature-measuring fluorescent optical fiber fire detector is small, 2.8mm in diameter, without any metal materials, electronic components, good insulation, 20cm withstands 100,000 volts voltage;

Full-year, all-weather security guardian: At least 25 years, 365 days a year, 24 hours a day real-time monitoring and analysis;

It reduces the blind area of monitoring and improves the safety of equipment: Positioning accuracy is 1 mm;

Cost savings: Directly installed in the temperature rise part, real-time recording and displaying monitoring point data to achieve unattended monitoring station objectives;

Maintenance basis is established: Fully grasp the operation of the equipment, can predict the aging of the equipment, so as to put forward the maintenance time and maintenance plan according to the operation status of the equipment;

Intelligent judgment: It can quickly judge and analyze the normal temperature, abnormal temperature and fire of the tested object.

 

4. Major Performance Indicators

image.png

image.png

 

5. Introduction of Main Components

The HQ series fluorescent optical fiber temperature monitoring system is selected as the on-line monitoring system for electric power connection in rail transit industry. A set of system is mainly composed of several optical fiber temperature sensors, a multi-channel optical fiber demodulator, monitoring host computer and human-machine exchange software.

5.1 HQ Series Fluorescent Fiber Temperature Demodulator

HQ series fluorescent optical fiber temperature demodulator receives real-time optical signal with temperature information from temperature-measuring fluorescent optical fiber fire detector, and demodulates it to temperature value to realize temperature measurement of monitored parts. When the actual measurement value is larger than the alarm setting value, the alarm signal sent out. They can work independently on a single computer, or can be used in multiple networking, and are suitable for application requirements of various scales.

5.2 Temperature-Measuring Fluorescent Optical Fiber Fire Detector

The probe size of temperature-measuring fluorescent fiber-optic fire detector is very small and can be directly installed at the measured point, which can measure temperature accurately and respond quickly. Its tail fiber is made of soft and strong special optical fiber, which has the advantages of high transmission bandwidth, stable signal, anti-electromagnetic interference, anti-flexure, high impact strength and fast connection.

The tail fiber sheath has the characteristics of high temperature resistance, aging resistance, corrosion resistance, high insulation, non-adherence and so on. It can adapt to the harsh environment of high voltage, high temperature, strong electromagnetic and so on.

5.3 Monitor Host

The monitoring host can receive and process the normal information, fault information and disaster information from the optical fiber temperature demodulator in real time, and quickly process and manage them. The monitoring host has the functions of fault monitoring, display, alarm and information exchange. At the same time, the remote monitoring can be realized through the network.

5.4 Men-Machine Interface

The main functions of the software system include real-time temperature local monitoring, real-time data remote monitoring, high/low temperature alarm, high/low temperature early warning, historical data playback, pre-alarm and post-alarm curve, temperature export to Excel and other functions.

6. Construction cases

Installation of monitoring host: The monitoring host of this system is installed in the monitoring cabinet of the substation control room, and a monitoring computer is set up in the central control station for remote monitoring.

Installation of HQ Series Optical Fiber Temperature Demodulator: The demodulator is installed on the back wall of the instrument panel in front of the switchgear to facilitate future maintenance.

image.png

image.png

Schematic Diagram of the Layout of the Switchgear in the HQ Series Fluorescent Optical Fiber Temperature Monitoring System

Installation of HQ-12 Temperature-measuring Fluorescent Optical Fiber Sensor

1. Installation on Switchgear Contacts

image.png

The main hotspot of switchgear is located at the joint of static and dynamic contacts, but this part is protected by insulating sleeve, and the space inside is very narrow. In order to measure the heating temperature of contacts more accurately, the diameter of HQ-12 temperature-measuring fluorescent optical fiber sensor is 2.8mm. It can extend into the inner of the sleeve from the rear of the sleeve along the confluence row. A high temperature resistant and high insulation installation clamp is designed specifically for the static contacts, which can fix the sensor firmly on the static contacts. 

When fixing the fluorescent optical fiber fire detector with a clamp, the sensor head is fixed in the fixed groove of the sensor first, and then the clamp and the sensor head are clamped on the cylinder of the static contact. During installation, the clamp is installed at the joint of the static contact and the bus bar to keep a safe distance from the movable contact.

2. Installation at Cable Joint of Switchgear

The fluorescent optical fiber fire detector for temperature measurement was pasted on the cable joint with special aviation silica gel and fixed with special strapping.

image.png

After the installation of the temperature-measuring fluorescent optical fiber fire detector is completed, the tail fibers are tied to the copper bars connected with the rear of the static contacts with insulating straps to prevent the temperature-measuring fluorescent optical fiber probe from hitting the adjacent contacts in case of falling off.

Inside Cabinet Wiring

In order not to affect the electrical distribution in the cabinet, as well as the future overhaul of the cabinet, cables and tail fibers in the cabinet should be as far as possible along the corner of the cabinet, or take a special trunk or bundle with the secondary cable in the cabinet.

image.png

HQ series transformer winding temperature measurement system, the optical fiber sensor probe is installed in winding coil in the process of transformer fabrication. Through flange penetrator, the internal and external optical signals are docked, and the temperature measurement host is analyzed and demodulated to realize real-time on-line temperature measurement.

Background communication: Real-time temperature data of field power equipment are uploaded to the backstage monitoring system through 485 parallel lines or optical cable transmission.

About insulation and anti-creeping: Temperature-measuring fluorescent optical fiber fire detector has high insulation, anti-creeping, anti-corrosion.

 

Attachment: Product Model

image.png

奥赛康:公司聚焦主营业务|奥赛康 十大机构看后市:A股跨年行情已经开启,转型牛深入推进,春季躁动行情可期,布局三大主线 “易中天”携手大涨,新易盛再创新高!光芯片迎新突破,双创龙头ETF(588330)盘中涨近3% 广东推出“粤味21”品牌IP 包含255道菜品 周期顺风、通胀回落、AI动荡、波动保护---这是高盛2026年“10大核心主题交易” 丹麦回应美国任命格陵兰岛特使:深感不满,召见美国驻丹麦大使 关于南京奥联汽车电子电器股份有限公司股票临时停牌的公告|电器股份 深北交易所火力全开,下周审9家,靓女先行!今年上会过会逼近110家!新股上市大提速,全年将超110家! 薛京:未来30年,将有80万亿家族企业财富面临传承 周期顺风、通胀回落、AI动荡、波动保护---这是高盛2026年“10大核心主题交易” [视频]李强主持召开国务院“十五五”规划《纲要草案》编制工作领导小组会议 丁薛祥出席 达丰设备公布中期业绩 推进业务结构优化 开拓多元市场布局 百余只货基收益率破“1” 基金公司集体限购保收益|货币基金 长安期货屈亚娟:印尼镍矿政策存扰动 但过剩压力尤在 2025年12月22日涨停板早知道:七大利好有望发酵|七大消息 加科思-B附属与阿斯利康订立许可与合作协议 以开发及商业化泛KRAS抑制剂JAB-23E73|加科思-B 【新思想引领新征程】长三角科技创新谱写新篇章 2025年底了,围海股份终于回复了2023年年报问询函|ST围海 链动津门,光耀新程:2025“工业光明之链”佛山照明天津研讨交流会成功举办|天津市 万科20亿债券展期方案再次被否,获一个月宽限期|万科 江苏农商联合银行获批参股高邮农商行 持股比例4.56%